Description
Detailed description of the individual modules is in the Catalog series B1/B1z
NOTE for PLC programmers!
Basic units of B1 not recognize automatically added Expansion Module. Therefore, you need a new extension module to add "manually", from the program WinProladder.
Digital I/O
Expansion units are connected to the right of the basic unit.
Stock Number | Number of Inputs | Number of Outputs | Output Type |
FAC-B1-8X | 8 | - | - |
FAC-B1-8YR | - | 8 | relay |
FAC-B1-8YT | - | 8 | trans. NPN |
FAC-B1-8YJ | - | 8 | trans. PNP |
FAC-B1-8XYR | 4 | 4 | relay |
FAC-B1-8XYT | 4 | 4 | trans. NPN |
FAC-B1-8XYJ | 4 | 4 | trans. PNP |
FAC-B1-16X | 16 | - | - |
FAC-B1-16YR | - | 16 | relay |
FAC-B1-16YT | - | 16 | trans. NPN |
FAC-B1-16YJ | - | 16 | trans. PNP |
FAC-B1-16XYR | 8 | 8 | relay |
FAC-B1-16XYT | 8 | 8 | trans. NPN |
FAC-B1-16XYJ | 8 | 8 | trans. PNP |
FAC-B1-24XYR | 14 | 10 | relay |
FAC-B1-24XYT | 14 | 10 | trans. NPN |
FAC-B1-24XYJ | 14 | 10 | trans. PNP |
FAC-B1-40XYR | 24 | 16 | relay |
FAC-B1-40XYT | 24 | 16 | trans. NPN |
FAC-B1-40XYJ | 24 | 16 | trans. PNP |
AIO Expansion Units (occupies the position of Port1)
AIO expansion units are connected on the left side of the basic unit. Only one analog expansion module can be connected.
You can connect to one communication module CM2 or CM5, that uses Port2.
Stock Number |
Analog Inputs | Analog Outputs |
FAC-B1-L2DA | - | 2 x 12bit (0~10V a 0~20mA) |
FAC-B1-L4AD | 4 x 12bit (0~10V a 0~20mA) |
- |
FAC-B1-L2A1D | 2 x 12bit (0~10V a 0~20mA) |
1 x 12bit (0~10V a 0~20mA) |
FAC-B1-L2A2D * |
2 x 12bit (0~10V a 0~20mA) |
2 x 12bit (0~10V a 0~20mA) |
*preparing
Communication Modules (occupies the position Port2 possibly Port1 too)
Communication modules are connected on the right side of the basic unit. Only one communication module can be connected.
Stock Number |
RS232 | RS485 | ETHERNET |
FAC-B1-CM2 | 1x (Port2) | - | - |
FAC-B1-CM5 | - | 1x (Port2) |
- |
FAC-B1-CM22 | 2x (Port2,1) |
- | - |
FAC-B1-CM55 | - | 2x (Port2,1) |
- |
FAC-B1-CM25 | 1x (Port2) |
1x (Port1) | - |
FAC-B1-CM25E | 1x (Port2) |
1x (Port1) | 1x |
FAC-B1-CM55E | 1x (Port2) |
1x (Port1) | 1x |
Support
Catalog: Catalog series B1/B1z